- Tariff metering, Volts, Amps, KW, Hz, cosphi, KWh and time-of-use metering.
- Waveform capture, transient capture, dip/swell monitoring, harmonics measurement (up to 63rd), symmetrical components, percent uptime.
- Power quality compliance monitoring (IEEE 519/1159, EN50160, IEC 61000-4-7/4-15).
- Sequence-of-events, coincident minimum/maximum, historical trends, and high-speed snapshot recording, 1 ms resolution timestamping, GPS time synchronisation.
- Communication ports: Ethernet, modem, RS-232/485, RS-485, front panel optical.

- Volts, Amps, KW, Hz, cosphi, KWh and time-of-use metering.
- Instrument transformer correction, transformer/line loss compensation.
- Total harmonic distortion (THD) and invidiual harmonics (THDi).
- Protocols: Modbus RTU slave/master, Modbus TCP, DNP 3.0, MV-90, IEC 61850.
- Ethernet and modem gateways to 31 devices on RS-485 port.
- On-board web server, email for alarms and data, FTP server.

- A true RMS meter, provides continuous monitoring of a three-phase system. It provides metering of current, voltage, real and reactive power, energy use, cost of power, power factor and frequency with 0.2% accuracy for voltage and currents.
- Panel mount with display, offers an easy local interface. Standard models have RS485 communications for programming and monitoring.
- Any of the assignable outputs may be used to trigger an alarm for specific applications. Simple alarm messages provide easy notification.
- Provides multiple communication ports that can provide data simultaneously to multiple masters such as SCADA, DCS, BMS etc. Meter supports both ModBus and DNP 3.0 protocol. A computer running EnerVistaTM software can change system setpoints, monitor values, status and alarms. Continuous monitoring minimizes process downtime by immediately identifying potential problems due to faults or changes.
- Power quality measurement: data logger (trending), harmonic analysis, voltage disturbance recorder (VDR), waveform capture, event recorders up to 150 and trace memory of data on all voltage and current inputs based on overvoltage, undervoltage, overcurrent or switch input state change.

- Scalable Power Quality platform product monitors four voltage and four current channels for each electrical cycle.
- Provides 1024 samples across eight channels every cycle.
- Revenue Metering accuracy 0.2%
- Voltage, current, neutral and earth current, power, frequency, power factor, demand, energy, and time-of-use metering.
- Power quality measurement: harmonic analysis up to the 127th, waveform capture sub-cycle transients detection, internal web page for the meter simplifies configuration and allows you to view real-time data.
- Virtual wiring correction capability can correct miswiring during commissioning, reducing the need to power down for correction.
- Configurable alarms for up to 10 events can help prevent issues or equipment damage.
- Four inputs for WAGES (water, air, gas, electricity, steam) data collection.
- Four outputs for connection to SCADA or control systems.
- Native EtherNet/IP™ communication port included.
- Option for a second communication port.
- System event snapshot capability.